Precautions when evaporative condenser installationPosition:Home > Blog > Industry News
When evaporative condensers are surrounded by a wall, into the outlet side of the installation should be 1800mm minimum spacing non inlet side of the minimum distance of 900mm.
When evaporative condensers are in three sides of real wall, side wall displaying empty, air inlet side of the minimum spacing should be 900mm, non-inlet side of the minimum spacing of 600mm.
When two evaporative condenser mounted in parallel, such as both the inlet side, the minimum inlet side between them, the minimum distance between them is 800mm, such as a station for the air inlet side, the other non-when the inlet side, the minimum distance of 900mm; such as when the two are not the inlet side, the minimum distance of 600mm
The centrifugal classifier or evaporative condenser water dish equipped with a coaxial connection times ah electric heating, the minimum distance should be increased to facilitate maintenance.